Generator Ratings & Configuration
Ratings:
Frequency 50Hz
Phases: 3
Prime output 80kVA / 64kW: This rating is applicable for supplying continuous electrical power at variable load. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
Standby output 88kVA / 70kW: This rating is applicable for supplying electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings.
Standard reference conditions: 25°C, 100m A.S.L, 30% relative humidity.
Configuration:
- 4-Stroke water cooled diesel engine.
 - Industrial silencer.
 - Coolant recovery tank.
 - Single bearing, 4 pole brushless alternator.
 - Anti-vibration mountings.
 - Integral fuel tank with fully bounded base protection.
 - Fuel level sensor.
 - Auto start control system with electronic digital control module DSE7420.
 - Output circuit breaker.
 - Emergency stop button.
 - High engine temperature and low oil pressure shutdown system.
 - 12V Starter battery with leads and switch.
 